110 kV Polymer Housed MOA Lightning arrester

 
 
 
 
 

The main features of 6-220kv products The Core column applied winding structure, Polymer Housed core pillar molded on the core column, with almost no internal air gap, and outstanding sealing performanceSimple in structure, small in size and light in weightPolymer Housed with flexible silicone rubber, explosion-proofZnO varistor as the core component is large in flow capacity which is much higher than that of the national standard GB11032, and with high reliability. With fully insulated tops, the product can be applied to the complete cabinet installation, which can reduce the designing size of cabinet.Products with detachment device can provide signals for quitting operation when failure occurs, avoiding arrester explosion, and it is maintenance-free.Polymer housed products with a CTI level of six, creepage distance meets the requirements of IV level in heavy pollution

TYPE YH5W5-96/250 YH10W5-96/250 YH5W5-100/260 YH10W5-100/260 YH5W5-102/266 YH10W5-102/266 YH5W5-108/281 YH10W5-108/281
Nominal System Voltage 110 110 110 110 110 110 110 110
Rated Voltage 96 96 100 100 102 102 108 108
Continuous Operating Voltage 75 75 78 78 79.6 79.6 84 84
Minmum Reference Voltage under 1 mA DC 140 140 145 145 148 148 157 157
Maximum Residul voltage under 1/5 µs Drop-off Discharge Current  288 (5KA) 280 (10KA) 299 (5KA) 291 (5KA) 305 (5KA) 297 (10KA) 323 (5KA) 315 (10KA)
Maximum Residul voltage under 8/20 µs Lightning  Discharge Current  250(5KA) 250 (10KA) 260 (5KA) 260(10KA) 266 (5KA) 266 (10KA) 281 (5KA) 281 (10KA)
Maximum Residul voltage under 30/60 µs Operating  Discharge Current  213 (0.25KA) 213 (0.5KA) 221 (0.25KA) 221 (0.5KA) 226 (0.25KA) 226 (0.5KA) 239 (0.25KA) 239 (0.5KA)
4/10 µs Large Current Shock Twice (KA) 100 100 100 100 100 100 100 100
2mS SW through-flow capacity A/18 600 600 600 600 600 600 600 600